Testing Types

Dyn1 vector group test: steps and expected reading

Dyn1 has a delta HV winding and a star with neutral LV winding, with clock number 1: LV lags HV by 30°. Compact-3, our portable turns ratio instrument with 18 vector groups, checks it with three quick tests and shows a − sign when the transformer is correct.

Vector groupDyn1
HV / LV windingDelta / star with neutral
Clock number1 – LV lags HV by 30°
Correct reading on Compact-3− (HT voltage around 180° from the LT excitation), shown in yellow
Tests3 (selector 1, 2, 3)

How to connect

Connect the HT leads R, Y, B to the HV terminals (1U, 1V, 1W), and the LT leads r, y, b and n (neutral) to the LV terminals (2u, 2v, 2w and the LV neutral). Make the connections once; the three tests are selected with the selector, no re-connection is needed.

Select Dyn1 as the vector group and enter the transformer’s calculated ratio (CR) from the nameplate.

Which windings are tested

Compact-3 applies a low voltage to one LT winding (the small letters) and measures the matching HT winding (the capital letters). The pairs for Dyn1 are:

Selector (sticker 1, 2, 3 / display R, Y, B)LT winding excitedHT winding measuredWhat you should see
1 (R)rnBR− sign, in yellow
2 (Y)ynRY− sign, in yellow
3 (B)bnYB− sign, in yellow

What the instrument shows

Turn the selector to 1, then 2, then 3 (the display shows R, then Y, then B) and note the ratio, deviation and the angle shown on the display for each step.

Compact-3 testing of Dyn1, phase rn/BR (selector 1 (R)), instrument display photo
Selector 1 (R): LT rn, HT BR
Compact-3 testing of Dyn1, phase yn/RY (selector 2 (Y)), instrument display photo
Selector 2 (Y): LT yn, HT RY
Compact-3 testing of Dyn1, phase bn/YB (selector 3 (B)), instrument display photo
Selector 3 (B): LT bn, HT YB

For Dyn1 the sign is − and the angle is around 180°. If the polarity is not what Dyn1 expects, the sign turns red (+) instead of yellow: check the leads, the selected vector group and the transformer’s internal connection.

How it looks in the Compact-3 software

The same readings can be read on a PC with the Compact-3 TTR software, saved in the table and printed as a PDF report.

Compact-3 testing of Dyn1, phase rn/BR (selector 1 (R)), TTR software screen
Software, selector 1 (R)
Compact-3 testing of Dyn1, phase yn/RY (selector 2 (Y)), TTR software screen
Software, selector 2 (Y)
Compact-3 testing of Dyn1, phase bn/YB (selector 3 (B)), TTR software screen
Software, selector 3 (B)

Review page

After the three tests the review page on the instrument lists all readings together.

Compact-3 testing of Dyn1, review page with ratio, deviation, HT and LT voltages and excitation current

Winding and clock diagram

Compact-3 testing of Dyn1, winding symbols and clock diagram with LV phasor r at 1 o'clock

Dyn1 and Dyn7

Dyn1 and Dyn7 are tested on the same windings; only the expected sign is different: Dyn1 shows −, Dyn7 shows +. A wrong choice between the two is the most common reason for a red sign.

Questions and answers

Which phases does Compact-3 test for Dyn1?

It tests LT rn against HT BR, LT yn against HT RY, LT bn against HT YB. The selector moves through 1, 2 and 3 (shown as R, Y and B on the display); no re-connection is needed.

What reading is correct for Dyn1?

A correct Dyn1 shows a - sign in front of the ratio, in yellow, close to the calculated ratio, with the HT voltage around 180 degrees from the LT excitation.

Why does Compact-3 show a red sign for Dyn1?

The polarity does not match Dyn1. Check the lead connections, that Dyn1 is the selected vector group and not Dyn7, and the transformer's internal connection.

See all vector groups of Compact-3 in Vector groups explained. Product page: Compact-3.

Other instruments for transformer testing

A vector group test is usually done together with a ratio test and a winding resistance test. These are the instruments we make for them.

InstrumentWhat it does
Compact-3Portable three-phase turns ratio instrument with battery backup. Tests all 18 vector groups in three steps.
VTRI-318SAutomatic turns ratio instrument, ratio 1-200 (1-2000 optional). Also supports all 18 vector groups.
TRM-1ATransformer winding resistance meter (1 A) for fast and accurate winding resistance testing, up to 10 MVA.
TRM-10DDual-channel transformer winding resistance meter, 0.2 mΩ to 2 kΩ, up to 20 MVA.
DVDF MeterDouble voltage, double frequency meter for the induced-voltage test: replaces two meters with one, more accurate and simpler.

Compact-3 and VTRI-318S both support all the vector groups on this page. For a price, a demo or help in choosing, please contact us.