PH0 (single phase) vector group test: steps and expected reading

PH0 has a single-phase HV winding and a single-phase LV winding, with clock number 0: no phase shift (0°). Compact-3, our portable turns ratio instrument with 18 vector groups, checks it with one test and shows a + sign when the transformer is correct.

Vector groupPH0 (single phase)
HV / LV windingSingle-phase / single-phase
Clock number0 – no phase shift (0°)
Correct reading on Compact-3+ (HT voltage around 0° from the LT excitation), shown in yellow
Tests1 (selector 1)

How to connect

Connect the HT leads R and N to the two ends of the HV winding and the LT leads r and n to the two ends of the LV winding (a single-phase transformer).

Select PH0 as the vector group and enter the transformer’s calculated ratio (CR) from the nameplate.

Which windings are tested

Compact-3 applies a low voltage to one LT winding (the small letters) and measures the matching HT winding (the capital letters). The pairs for PH0 are:

Selector (sticker 1, 2, 3 / display R, Y, B)LT winding excitedHT winding measuredWhat you should see
1 (R)rnRN+ sign, in yellow

What the instrument shows

Turn the selector to 1 (the display shows R) and note the ratio, deviation and the angle shown on the display for each step.

Compact-3 testing of PH0, phase rn/RN (selector 1 (R)), instrument display photo
Selector 1 (R): LT rn, HT RN

For PH0 the sign is + and the angle is around 0°. If the polarity is not what PH0 expects, the sign turns red (−) instead of yellow: check the leads, the selected vector group and the transformer’s internal connection.

How it looks in the Compact-3 software

The same readings can be read on a PC with the Compact-3 TTR software, saved in the table and printed as a PDF report.

Compact-3 testing of PH0, phase rn/RN (selector 1 (R)), TTR software screen
Software, selector 1 (R)

Review page

After the test the review page on the instrument lists all readings together.

Compact-3 testing of PH0, review page with ratio, deviation, HT and LT voltages and excitation current

Winding and clock diagram

Compact-3 testing of PH0, winding symbols and clock diagram with LV phasor r at 12 o'clock

PH0 and PH6

PH0 and PH6 are tested on the same windings; only the expected sign is different: PH0 shows +, PH6 shows −. A wrong choice between the two is the most common reason for a red sign.

Questions and answers

Which phases does Compact-3 test for PH0?

It tests LT rn against HT RN.

What reading is correct for PH0?

A correct PH0 shows a + sign in front of the ratio, in yellow, close to the calculated ratio, with the HT voltage around 0 degrees from the LT excitation.

Why does Compact-3 show a red sign for PH0?

The polarity does not match PH0. Check the lead connections, that PH0 is the selected vector group and not PH6, and the transformer's internal connection.

See all vector groups of Compact-3 in Vector groups explained. Product page: Compact-3.

Other instruments for transformer testing

A vector group test is usually done together with a ratio test and a winding resistance test. These are the instruments we make for them.

InstrumentWhat it does
Compact-3Portable three-phase turns ratio instrument with battery backup. Tests all 18 vector groups in three steps.
VTRI-318SAutomatic turns ratio instrument, ratio 1-200 (1-2000 optional). Also supports all 18 vector groups.
TRM-1ATransformer winding resistance meter (1 A) for fast and accurate winding resistance testing, up to 10 MVA.
TRM-10DDual-channel transformer winding resistance meter, 0.2 mΩ to 2 kΩ, up to 20 MVA.
DVDF MeterDouble voltage, double frequency meter for the induced-voltage test: replaces two meters with one, more accurate and simpler.

Compact-3 and VTRI-318S both support all the vector groups on this page. For a price, a demo or help in choosing, please contact us.