How to test a YNyn6 (Yy6) transformer with Compact-3
YNyn6 has a star with neutral HV winding and a star with neutral LV winding, with clock number 6: LV lags HV by 180°. It is also written Yy6. Compact-3, our portable turns ratio instrument with 18 vector groups, checks it with three quick tests and shows a − sign when the transformer is correct.
| Vector group | YNyn6 (Yy6) |
|---|---|
| HV / LV winding | Star with neutral / star with neutral |
| Clock number | 6 – LV lags HV by 180° |
| Correct reading on Compact-3 | − (HT voltage around 180° from the LT excitation), shown in yellow |
| Tests | 3 (selector 1, 2, 3) |
How to connect
Connect the HT leads R, Y, B and N (neutral) to the HV terminals (1U, 1V, 1W and the HV neutral), and the LT leads r, y, b and n (neutral) to the LV terminals (2u, 2v, 2w and the LV neutral). Make the connections once; the three tests are selected with the selector, no re-connection is needed.
Select YNyn6 as the vector group and enter the transformer’s calculated ratio (CR) from the nameplate.
Which windings are tested
Compact-3 applies a low voltage to one LT winding (the small letters) and measures the matching HT winding (the capital letters). The pairs for YNyn6 are:
| Selector (sticker 1, 2, 3 / display R, Y, B) | LT winding excited | HT winding measured | What you should see |
|---|---|---|---|
| 1 (R) | rn | RN | − sign, in yellow |
| 2 (Y) | yn | YN | − sign, in yellow |
| 3 (B) | bn | BN | − sign, in yellow |
What the instrument shows
Turn the selector to 1, then 2, then 3 (the display shows R, then Y, then B) and note the ratio, deviation and the angle shown on the display for each step.
![]() Selector 1 (R): LT rn, HT RN | ![]() Selector 2 (Y): LT yn, HT YN | ![]() Selector 3 (B): LT bn, HT BN |
For YNyn6 the sign is − and the angle is around 180°. If the polarity is not what YNyn6 expects, the sign turns red (+) instead of yellow: check the leads, the selected vector group and the transformer’s internal connection.
How it looks in the Compact-3 software
The same readings can be read on a PC with the Compact-3 TTR software, saved in the table and printed as a PDF report.
![]() Software, selector 1 (R) | ![]() Software, selector 2 (Y) | ![]() Software, selector 3 (B) |
Review page
After the three tests the review page on the instrument lists all readings together.

Winding and clock diagram
YNyn6 and YNyn0
YNyn6 and YNyn0 are tested on the same windings; only the expected sign is different: YNyn6 shows −, YNyn0 shows +. A wrong choice between the two is the most common reason for a red sign.
Questions and answers
Which phases does Compact-3 test for YNyn6?
It tests LT rn against HT RN, LT yn against HT YN, LT bn against HT BN. The selector moves through 1, 2 and 3 (shown as R, Y and B on the display); no re-connection is needed.
What reading is correct for YNyn6?
A correct YNyn6 shows a - sign in front of the ratio, in yellow, close to the calculated ratio, with the HT voltage around 180 degrees from the LT excitation.
Why does Compact-3 show a red sign for YNyn6?
The polarity does not match YNyn6. Check the lead connections, that YNyn6 is the selected vector group and not YNyn0, and the transformer's internal connection.
See all vector groups of Compact-3 in Vector groups explained. Product page: Compact-3.
Other instruments for transformer testing
A vector group test is usually done together with a ratio test and a winding resistance test. These are the instruments we make for them.
| Instrument | What it does |
|---|---|
| Compact-3 | Portable three-phase turns ratio instrument with battery backup. Tests all 18 vector groups in three steps. |
| VTRI-318S | Automatic turns ratio instrument, ratio 1-200 (1-2000 optional). Also supports all 18 vector groups. |
| TRM-1A | Transformer winding resistance meter (1 A) for fast and accurate winding resistance testing, up to 10 MVA. |
| TRM-10D | Dual-channel transformer winding resistance meter, 0.2 mΩ to 2 kΩ, up to 20 MVA. |
| DVDF Meter | Double voltage, double frequency meter for the induced-voltage test: replaces two meters with one, more accurate and simpler. |
Compact-3 and VTRI-318S both support all the vector groups on this page. For a price, a demo or help in choosing, please contact us.