Dyn11 transformer test: connections and reading
Dyn11 has a delta HV winding and a star with neutral LV winding, with clock number 11: LV lags HV by 330° (the same as leading by 30°). Compact-3, our portable turns ratio instrument with 18 vector groups, checks it with three quick tests and shows a + sign when the transformer is correct.
| Vector group | Dyn11 |
|---|---|
| HV / LV winding | Delta / star with neutral |
| Clock number | 11 – LV lags HV by 330° (the same as leading by 30°) |
| Correct reading on Compact-3 | + (HT voltage around 0° from the LT excitation), shown in yellow |
| Tests | 3 (selector 1, 2, 3) |
How to connect
Connect the HT leads R, Y, B to the HV terminals (1U, 1V, 1W), and the LT leads r, y, b and n (neutral) to the LV terminals (2u, 2v, 2w and the LV neutral). Make the connections once; the three tests are selected with the selector, no re-connection is needed.
Select Dyn11 as the vector group and enter the transformer’s calculated ratio (CR) from the nameplate.
Which windings are tested
Compact-3 applies a low voltage to one LT winding (the small letters) and measures the matching HT winding (the capital letters). The pairs for Dyn11 are:
| Selector (sticker 1, 2, 3 / display R, Y, B) | LT winding excited | HT winding measured | What you should see |
|---|---|---|---|
| 1 (R) | rn | RY | + sign, in yellow |
| 2 (Y) | yn | YB | + sign, in yellow |
| 3 (B) | bn | BR | + sign, in yellow |
What the instrument shows
Turn the selector to 1, then 2, then 3 (the display shows R, then Y, then B) and note the ratio, deviation and the angle shown on the display for each step.
![]() Selector 1 (R): LT rn, HT RY | ![]() Selector 2 (Y): LT yn, HT YB | ![]() Selector 3 (B): LT bn, HT BR |
For Dyn11 the sign is + and the angle is around 0°. If the polarity is not what Dyn11 expects, the sign turns red (−) instead of yellow: check the leads, the selected vector group and the transformer’s internal connection.
How it looks in the Compact-3 software
The same readings can be read on a PC with the Compact-3 TTR software, saved in the table and printed as a PDF report.
![]() Software, selector 1 (R) | ![]() Software, selector 2 (Y) | ![]() Software, selector 3 (B) |
Review page
After the three tests the review page on the instrument lists all readings together.

Winding and clock diagram
Dyn11 and Dyn5
Dyn11 and Dyn5 are tested on the same windings; only the expected sign is different: Dyn11 shows +, Dyn5 shows −. A wrong choice between the two is the most common reason for a red sign.
Questions and answers
Which phases does Compact-3 test for Dyn11?
It tests LT rn against HT RY, LT yn against HT YB, LT bn against HT BR. The selector moves through 1, 2 and 3 (shown as R, Y and B on the display); no re-connection is needed.
What reading is correct for Dyn11?
A correct Dyn11 shows a + sign in front of the ratio, in yellow, close to the calculated ratio, with the HT voltage around 0 degrees from the LT excitation.
Why does Compact-3 show a red sign for Dyn11?
The polarity does not match Dyn11. Check the lead connections, that Dyn11 is the selected vector group and not Dyn5, and the transformer's internal connection.
See all vector groups of Compact-3 in Vector groups explained. Product page: Compact-3.
Other instruments for transformer testing
A vector group test is usually done together with a ratio test and a winding resistance test. These are the instruments we make for them.
| Instrument | What it does |
|---|---|
| Compact-3 | Portable three-phase turns ratio instrument with battery backup. Tests all 18 vector groups in three steps. |
| VTRI-318S | Automatic turns ratio instrument, ratio 1-200 (1-2000 optional). Also supports all 18 vector groups. |
| TRM-1A | Transformer winding resistance meter (1 A) for fast and accurate winding resistance testing, up to 10 MVA. |
| TRM-10D | Dual-channel transformer winding resistance meter, 0.2 mΩ to 2 kΩ, up to 20 MVA. |
| DVDF Meter | Double voltage, double frequency meter for the induced-voltage test: replaces two meters with one, more accurate and simpler. |
Compact-3 and VTRI-318S both support all the vector groups on this page. For a price, a demo or help in choosing, please contact us.






