Home › Knowledge Center › Want to test YNd5 transformers? Use Compact-3
Testing Types

Want to test YNd5 transformers? Use Compact-3

YNd5 has a star with neutral HV winding and a delta LV winding, with clock number 5: LV lags HV by 150°. Compact-3, our portable turns ratio instrument with 18 vector groups, checks it with three quick tests and shows a + sign when the transformer is correct.

Vector groupYNd5
HV / LV windingStar with neutral / delta
Clock number5 – LV lags HV by 150°
Correct reading on Compact-3+ (HT voltage around 0° from the LT excitation), shown in yellow
Tests3 (selector 1, 2, 3)

How to connect

Connect the HT leads R, Y, B and N (neutral) to the HV terminals (1U, 1V, 1W and the HV neutral), and the LT leads r, y, b to the LV terminals (2u, 2v, 2w). Make the connections once; the three tests are selected with the selector, no re-connection is needed.

Select YNd5 as the vector group and enter the transformer’s calculated ratio (CR) from the nameplate.

Which windings are tested

Compact-3 applies a low voltage to one LT winding (the small letters) and measures the matching HT winding (the capital letters). The pairs for YNd5 are:

Selector (sticker 1, 2, 3 / display R, Y, B)LT winding excitedHT winding measuredWhat you should see
1 (R)ryYN+ sign, in yellow
2 (Y)ybBN+ sign, in yellow
3 (B)brRN+ sign, in yellow

What the instrument shows

Turn the selector to 1, then 2, then 3 (the display shows R, then Y, then B) and note the ratio, deviation and the angle shown on the display for each step.

Compact-3 testing of YNd5, phase ry/YN (selector 1 (R)), instrument display photo
Selector 1 (R): LT ry, HT YN
Compact-3 testing of YNd5, phase yb/BN (selector 2 (Y)), instrument display photo
Selector 2 (Y): LT yb, HT BN
Compact-3 testing of YNd5, phase br/RN (selector 3 (B)), instrument display photo
Selector 3 (B): LT br, HT RN

For YNd5 the sign is + and the angle is around 0°. If the polarity is not what YNd5 expects, the sign turns red (−) instead of yellow: check the leads, the selected vector group and the transformer’s internal connection.

How it looks in the Compact-3 software

The same readings can be read on a PC with the Compact-3 TTR software, saved in the table and printed as a PDF report.

Compact-3 testing of YNd5, phase ry/YN (selector 1 (R)), TTR software screen
Software, selector 1 (R)
Compact-3 testing of YNd5, phase yb/BN (selector 2 (Y)), TTR software screen
Software, selector 2 (Y)
Compact-3 testing of YNd5, phase br/RN (selector 3 (B)), TTR software screen
Software, selector 3 (B)

Review page

After the three tests the review page on the instrument lists all readings together.

Compact-3 testing of YNd5, review page with ratio, deviation, HT and LT voltages and excitation current

Winding and clock diagram

Compact-3 testing of YNd5, winding symbols and clock diagram with LV phasor r at 5 o'clock

YNd5 and YNd11

YNd5 and YNd11 are tested on the same windings; only the expected sign is different: YNd5 shows +, YNd11 shows −. A wrong choice between the two is the most common reason for a red sign.

Questions and answers

Which phases does Compact-3 test for YNd5?

It tests LT ry against HT YN, LT yb against HT BN, LT br against HT RN. The selector moves through 1, 2 and 3 (shown as R, Y and B on the display); no re-connection is needed.

What reading is correct for YNd5?

A correct YNd5 shows a + sign in front of the ratio, in yellow, close to the calculated ratio, with the HT voltage around 0 degrees from the LT excitation.

Why does Compact-3 show a red sign for YNd5?

The polarity does not match YNd5. Check the lead connections, that YNd5 is the selected vector group and not YNd11, and the transformer's internal connection.

See all vector groups of Compact-3 in Vector groups explained. Product page: Compact-3.

Other instruments for transformer testing

A vector group test is usually done together with a ratio test and a winding resistance test. These are the instruments we make for them.

InstrumentWhat it does
Compact-3Portable three-phase turns ratio instrument with battery backup. Tests all 18 vector groups in three steps.
VTRI-318SAutomatic turns ratio instrument, ratio 1-200 (1-2000 optional). Also supports all 18 vector groups.
TRM-1ATransformer winding resistance meter (1 A) for fast and accurate winding resistance testing, up to 10 MVA.
TRM-10DDual-channel transformer winding resistance meter, 0.2 mΩ to 2 kΩ, up to 20 MVA.
DVDF MeterDouble voltage, double frequency meter for the induced-voltage test: replaces two meters with one, more accurate and simpler.

Compact-3 and VTRI-318S both support all the vector groups on this page. For a price, a demo or help in choosing, please contact us.