Section: Testing Examples
Today demand of pure sinewave inverter/UPS is increasing beacuse square wave UPS/Inverter can not run various equipments. So we have taken a sinewave UPS for testing.
We can know the purity of sine wave inveter by harmonics analysis. A square wave inverter has very high voltage THD at output whereas pure sinewave has zero THD(Ideal).
UPS Harmonic Test Report
Date : 11-11-2014
|
Standard |
UL1778 article 49 Harmonic Distortion Test |
|
Instrument Under Test |
UPS 600VA |
|
Company Name |
Sukm |
|
Rated Voltage and Load |
12V,50A |
|
Battery Type |
Tubular Battery |
|
Test Condition |
On battery source (Assuming full charge battery) |
Load Pattern-
On 10% Load
|
Load Condition |
Voltage |
Voltage Harmonics |
|
55.38 VA |
227 V |
2.843% |
Comments –
On 20% Load
|
Load Condition(VA) |
Voltage |
Voltage Harmonics |
|
124.78 |
227.3 |
2.611 |
Comment –
On 25% Load
|
Load Condition(VA) |
Voltage |
Voltage Harmonics |
|
153.9 |
226.3 |
2.755 |
Comment –
On 40% Load
|
Load Condition(VA) |
Voltage |
Voltage Harmonics |
|
194.53 |
223.6 |
2.835 |
Comment –
On 50% Load
|
Load Condition(VA) |
Voltage |
Voltage Harmonics |
|
302.8 |
222.8 |
3.596 |
Comment –
Summary –
Testing Instrument – SPEA-1
Test Done By – Himanshu Sharma (Electronic Testing)